Feature●The wall duct is suitable for the RKL 300 and RKL 360 air conditioners●A core hole with a diameter of 135 mm in the outer wall is required for the installation of the wall bushing●Box contents include a wall bushingDescription
Remko wall duct for exhaust hose mobile air conditioning
- Suitable for room air conditioner RKL 300 and RKL 360.
Installation instructions: - 1. Create a core hole in the outer wall (max. Wall thickness 480 mm) with a diameter of at least 135 mm. Please note possible supply lines in this area!
- 2. Insert the slider pipe into the created wall opening so that the outer tube (large diameter) is on the inside of the wall. To avoid cold bridges, insulate the telescopic tube with suitable insulation materials.
- 3. Wall the slider pipe in the core hole so that the flush is provided on both wall sides.
- 4. Attach the protective grille to the outside of the wall with 4 screws. Install the grille in compliance with rain repellency.
- 5. Insert the check valve inside and attach it with 4 screws. The lettering on the top of the check flap must be seen from the inside.
- 6. When the device is out of use, e.g. before the start of winter time, close the opening in the check flap with the closure lid to prevent air circulation.